Sungrow premium 5kw Fault codes.

Sungrow premium 5kw Fault codes.

Fault Code Description Troubleshooting
2 The grid voltage exceeds 1. Check the voltage of the grid.
inverter allowable 2. If the grid voltage exceeds the permissible range of inverter protection parameters, ask utility grid company for solution.
upper limit. 3. If the grid voltage is within the permissible range, contact Sungrow Service Dept.
3 Grid transient voltage 1. This is a short-term fault due to grid condition. Wait a moment for inverter recovery.
exceeds the permissible 2. If the fault still exists, please contact Sungrow Service Dept.
range  
4 The grid voltage is below 1. Check the grid voltage.
inverter’s allowable 2. If the grid voltage exceeds the permissible range of inverter protection parameters, ask utility grid company for solution.
lower limit. 3. If the grid voltage is within the permissible range, contact Sungrow Service Dept.
5 The grid voltage is too low. 1. This is a short-term fault due to grid condition. Wait a moment for inverter recovery.
2. If the fault still exists, please contact Sungrow Service Dept.
6 The AC output current 1. The inverter will resume if the output current falls below the protection value.
exceeds inverter 2. If the fault still exists, please contact Sungrow Service Dept.
allowable upper limit.  
7 Transient AC overcurrent 1. The inverter will self-recover after several seconds.
2. If the fault still exists, please contact Sungrow Service Dept.
8 The grid frequency exceeds inverter allowable upper limit. 1. Check the grid frequency.
2. If the grid frequency exceeds the permissible range of inverter protection parameters, ask utility grid company for solution.
9 The grid frequency is below the inverter allowable lower limit. 3. If the grid frequency is within the permissible range, contact Sungrow Service Dept.
10 Islanding 1. Check whether AC circuit breaker is triggered.
2. Check whether AC cables are all firmly connected.
3. Check whether grid is not in service.
4. If all conditions are OK and this fault still occurs in the LCD screen, contact Sungrow Service Dept.
11 The DC component of AC current exceeds inverter limit. 1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact Sungrow Service Dept.
12 A failure current is detected. 1. Check the PV strings for ground fault.
2.  If the fault occurs repeatedly, contact Sungrow Service Dept.
14 The average grid voltage exceeds the permissible range for over 10 minutes. 1. Wait a moment for inverter recovery.
2. Check the voltage of the grid. If the grid voltage exceeds the permissible range of inverter protection parameters, ask utility grid company for solution.
3. If the fault occurs repeatedly, contact Sungrow Service Dept.
15 The grid voltage exceeds the permissible range 1. Check the model of the AC cables.
2.Wait a moment for inverter recovery.
3. If the grid voltage exceeds the permissible range of inverter protection parameters, ask utility grid company for solution.
4.  If the fault occurs repeatedly, contact Sungrow Service Dept.
16 The bus voltage or power is high. 1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact Sungrow Service Dept.
19 The transient bus voltage is high. 1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact Sungrow Service Dept.
20 The bus voltage is high. 1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact Sungrow Service Dept.
21 PV1 input overcurrent is detected Check the layout and the wiring of PV1 input.
22 PV2 input overcurrent is detected Check the layout and the wiring of PV2 input.
36 The temperature of radiator is too high. 1. Check whether the placement of inverter is correctly.
2. Check whether the inverter operating ambient temperature is more than the range indicated in the specification.
3. Check whether the AC output power exceeds the nominal power.
37 The internal temperature of inverter is too high 4. If the fault still exists, please contact Sungrow.
38 Relay fault is detected 1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact Sungrow Service Dept.
39 The insulation resistance is low. (ISO-flt) 1. Check whether the positive and negative of PV panels is short-circuited with ground lead.
2.  Wait a moment for inverter recovery.
3. If the fault occurs repeatedly, contact Sungrow Service Dept.
41 Leakage current self-test abnormality 1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact Sungrow Service Dept.
47 The PV configuration mode set in the phone application interface is not in accordance with the configuration in the connection cabinet. 1. Disconnect the inverter.
2. Re-select PV configuration mode and re-connect PV strings.
48 Sampling channel failure 1. Wait a moment for inverter recovery.
2. If the fault occurs repeatedly, contact Sungrow Service Dept.
53 Auxiliary DSP detects grid voltage exceeds set protection value 1. Check the grid voltage.
2. If the grid voltage exceeds the permissible range of inverter protection parameters, ask utility grid company for solution.
3. If the grid voltage is within the permissible range, contact Sungrow Service Dept.
54 Auxiliary DSP detects grid frequency exceeds set protection value 1. Check the grid frequency.
2. If the grid frequency exceeds the permissible range of inverter protection parameters, ask utility grid company for solution.